Series 616WL Differential Pressure Transmitter

Differential Pressure Transmitter
Low Ranges Down to 0.25" w.c. (60 Pa), NEMA 4X Housing

$0.00

Low Ranges Down to 0.25" w.c. (60 Pa), NEMA 4X Housing

The SERIES 616WL Differential Pressure Transmitter senses very low pressures of air and non-combustible, compatible gases and sends a standard 4-20 mA output signal. All models, including those featuring the 3 digit LCD digital read-out, are factory calibrated to specific ranges as listed in the chart below.

Positive, negative and differential pressures can be measured within a full span accuracy of ±0.50%. This weatherproof unit is enclosed in a polycarbonate case, designed to meet (IP66/NEMA 4X). Internal digital push button zero and span allow for quick and simple field calibration.

Product Applications

  • Low pressure applications
  • Outdoor HVAC
  • Dust collection
  • Roof-top equipment
More Information
Model Chart
EXAMPLE 616WL 1 AT Series 616WL-1-AT Differential Pressure Transmitter, range 0-0.10" w.c., with aluminum tag.
SERIES 616WL     Differential Pressure Transmitter
RANGE   2
4
12
14
22
24
32
34
  0 to 0.25" w.c.
0 to 1.00" w.c.
0 to ±0.25" w.c.
0 to ±1.00" w.c.
0 to 60 Pa
0 to 125 Pa
0 to ±60 Pa
0 to ±125 Pa
OPTIONS     AT
LCD
NIST
PRESETD
Aluminum Tag
Liquid Crystal Display
NIST Certificate of Calibration
LCD Display Set to 0-100%
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±0.50% F.S., display accuracy ±0.5%.
Stability:±1% F.S./yr.
Temperature Limits: 0 to 140°F (-17.8 to 60°C).
Compensated Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Pressure Limits: See Catalog page.
Thermal Effect: ±0.02% F.S./°F (0.036% F.S./°C).
Power Requirements: 12 to 30 VDC (2-wire).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Digital, Push Button Adj.
Loop Resistance: DC; 0 to 900 Ω maximum.
Current Consumption: DC; 38 mA maximum.
Electrical Connections: Screw-type terminal block.
Process Connections: Barbed, dual size to fit 1/8" and 3/16" (3.12 and 4.76 mm) I.D. rubber or vinyl tubing.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Vertical, consult factory for other position orientations.
Weight: Without LCD 17 oz (482 g); with LCD 18 oz (510 g).
Agency Approvals: CE.
  • NEMA 4X rated enclosure provides protection in harsh environments permitting outdoor monitoring or in areas where dust and particulate matter exists
  • Easy to read LCD display provides immediate local alerts allowing corrective action to be taken quicker to eliminate the problem from becoming widespread
  • Zero and span controls provides easy calibration checks and shorter installation time to get device running and monitoring
  • High precision accuracy at low pressure ranges provides exceptional accuracy for insuring tight-control and minimizing costly out of specification conditions